All Spec Sheets
Electro Cable
2kV PV Wire
Aluminum Building Wire|Aluminum
(847) 376-9187 · (954) 526-8042·sales@electrocable.us
Construction Parameters
  • INSULATION: Flame retardant Cross-Linked Polyethylene (XLPE)
  • INSULATION COLOR: Black and Red
Product Features
  • TEMPERATURE RATINGS: 90°C Dry, 90°C Wet. Rated for direct burial, moisture resistant, meets cold bend & cold impact test at -40°C
Voltage Rating

2,000 V for interconnection wiring of grounded and ungrounded photovoltaic power systems as described in Section 690.31 (A) and other applicable parts of the National Electrical Code (NEC), NFPA 70

Standards & Approvals
  • UL 44 Type RHH/RHW-2, 2000V, UV/Sunlight Resistant
  • UL 854 Type USE-2
  • UL 4703 Type PV
  • ASTM B800 , B801, B836
  • Flame Test: UL 1581 VW-1
  • Sizes 1/0 AWG and larger rated for CT use
  • ROHS, EPA 40 CFR, Part 26, Subpart C, heavy metals per Table 1, TLCP method
Physical Characteristics
2kV PV Wire
Conductor SizeStrandingConductor Nominal DiameterInsulationThicknessNominal OutsideDiameterAL WeightNominal Net WeightMaximum Pulling TensionMinimum Bending Radius*
AWG/KcmilNo.inchmilsinchlb/1000ftlb/1000ftlbinch
4/0^19/w0.4751050.68520029412702.7
250^36/w0.5201200.76023636315003.0
300^36/w0.5701200.81028241218003.2
35036/w0.6141200.85432947921003.4
40036/w0.6571200.89737754824003.6
50036/w0.7361200.97647168530003.9
60060/w0.8131351.08356582236005.4
75060/w0.9081351.178706102745005.9
1000^60/w1.0601351.330944117060006.7

Data are approximate and subject to normal manufacturing tolerances.

^Non-stock item

*Minimum bending radius shown applies to permanent training. Larger radius should be used during cable pulling.

x Other colors available as non-stock items

Electrical Characteristics
2kV PV Wire
Conductor SizeDC Resistance@ 25°CAC Resistance@ 75°CInductive Reactance+Ampacity@ 75°C*Ampacity@ 90°C*
AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftampsamps
4/0^0.0840.1000.041180205
250^0.0710.0860.041205230
300^0.0590.0710.041230260
3500.0510.0620.040250280
4000.0440.0540.040270305
5000.0350.0440.039310350
6000.0290.0360.039340385
7500.0240.0310.038385435
1000^0.0180.0250.037445500

*Ampacities are based on NEC 2023 Table 310.16, Ampacities of Insulated Conductors in Raceway, Cable, or Earth (Directly Buried). Not more than 3 current-carrying conductors. Ambient temperature of 30°C.

+Inductive reactance based on NEC 2023, 3-Phase, 60 Hz, 75°C, 3-1/C in Conduit (PVC or Aluminum).

^Non-stock item

x Other colors available as non-stock items