Aluminum Building Wire|Aluminum
(847) 376-9187 · (954) 526-8042·sales@electrocable.us
Application

Electro Cable's aluminum MC Cable can be used to replace wire and conduit in applications such as cable tray, power lighting, service feeders and branch circuits as permitted by the National Electrical Code. Suitable for use in concealed or exposed installations including environmental air spaces per NEC 300.22 (when unjacketed), and in vertical applications if installed per the requirements of NEC 300.19(A) and 330.30. Suitable for Class I Div 2, Class II Div 2, Class III Div 1 Hazardous Locations. PVC-jacketed MC cable is sunlight resistant and suitable for use in wet locations per NEC 330.10(A)(11).

Product Features
  • Type MC cable is constructed with 3 or 4 8000 series compact stranded aluminum XHHW-2 conductors cabled with a bare or insulated 8000 series aluminum grounding conductor. A binder identification baring tape is wrapped over the cabled assembly. Aluminum armor is interlocked over the conductor assembly. All insulated conductors are phase identified.
Standards
  • UL 44
  • UL 1569
  • ASTM B800, B801
  • ICEA S-95-658 (NEMA WC 70)
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Compliant to RoHS, Directive 2011/65/EU
MC Cable
Aluminum MC Cable
Cond. Size AWG or MCMSub Assembly (O.D.)Overall Diameter (in)Weight per 1000 ft. (lbs)Ampacity (amps) 75° CAmpacity (amps) 90° C
Three Conductor with Ground
6-6-6-60.570.782375055
4-4-4-60.660.882986575
2-2-2-60.78141190100
1-1-1-40.891.11496100115
1/0-1/0-1/0-40.971.19578120135
2/0-2/0-2/0-41.061.27678135150
3/0-3/0-3/0-41.161.38833155175
4/0-4/0-4/0-21.271.591089180205
250-250-250-21.421.731275205230
300-300-300-21.511.791361230260
350-350-350-21.621.941653250280
400-400-400-11.722.041830270305
500-500-500-11.882.22177310350
600-600-600-12.12.42608340385
750-750-750-1/02.32.53118385435
Four Conductor with Ground
6-6-6-6-60.700.922784044
4-4-4-4-60.771.043605260
2-2-2-2-60.891.104827280
1-1-1-1-40.991.216198092
1/0-1/0-1/0-1/0-41.081.372796108
2/0-2/0-2/0-2/0-41.181.4858108120
3/0-3/0-3/0-3/0-41.31.611138124140
4/0-4/0-4/0-4/0-21.421.741374144164
250-250-250-250-11.581.91634164184
300-300-300-300-11.701.991722184208
350-350-350-350-1/01.822.131969200224
400-400-400-400-1/01.912.202189216244
500-500-500-500-2/02.112.352653248280
500-500-500-500-2502.302.612822248280
600-600-600-600-2/02.352.673177272308
600-600-600-600-4002.622.943494272308
750-750-750-750-3/02.602.863858308348

Ampacities shown are based on the National Electrical Code (NFPA 70) Table 310.16. Ampacities have been adjusted for more than three current-carrying conductors.

Standard lengths are subject to normal manufacturing tolerance of +/- 10%

Other ground sizes are available upon request. MC cables in parallel must have a ground size meeting the minimum size specified in NEC Table 250.122 based on the rating or setting of the over-current protection device. Cables with undersized grounds will not meet code and are subject to rejection by the electrical inspector. Where necessary to comply with NEC 250.4(A)(5) or (B)(4), larger ground sizes may be required.

Image shows standard colors and bare ground. Green insulated ground and alternate phase insulation colors are available, e.g. high voltage colors (Brown/Orange/Yellow/Gray), upon request.