All Spec Sheets
Electro Cable
600 Volt Triplex
Aluminum URD & Overhead|Aluminum
(847) 376-9187 · (954) 526-8042·sales@electrocable.us
Application

Directly buried or installed in ducts for 600 volt secondary distribution.

Product Features
  • Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral, triple yellow striped or solid yellow. Black neutrals may be specified if desired.
Standards
  • UL Standard 854 for Type USE-2, ASTM B-230, B-231 and
  • ICEA S-105-692, Federal Specification JC-30B NEC
600V Secondary UD - Triplex
600 Volt Triplex
Code WordPhase ConductorsNeutral ConductorSingle Phase Conductor (in)Outside Diameter (in)Weight per 1000 ft. (lbs)Ampacity
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandInsulation Thickness (MLS)Direct BurialIn Duct
Erksine67/w6067/w60.299.6461439570
Vassar47/w6047/w60.345.75420312590
Stephens27/w6047/w60.403.842264165120
Ramapo27/w6027/w60.403.874294165120
Brenau1/019/w8027/w60.5221.064408215160
Bergen1/019/w801/019/w80.5221.133465215160
Converse2/019/w80119/w80.5661.174502245180
Hunter2/019/w802/019/w80.5661.228560245180
Hollins3/019/w801/019/w80.6161.276606280205
Sweetbriar4/019/w802/019/w80.6721.389739315240
Monmouth4/019/w804/019/w80.6721.457828315240
Pratt25037/w953/019/w80.7481.538893345265
Wesleyan35037/w954/019/w80.8511.7361166415320
Rider50037/w9535037/w95.9792.0351663495395
Fairfield75061/w11050037/w951.1182.8602304615525

Ampacity: 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor for three conductor triplex with neutral carrying only unbalanced load.

All Yellow Extruded Stripe, cable is XLP insulation.

* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.

The above data are approximate and subject to normal manufacturing tolerances.