Aluminum URD & Overhead|Aluminum
(847) 376-9187 · (954) 526-8042·sales@electrocable.us
Application

Directly buried or installed in ducts for 600 volt secondary distribution.

Product Features
  • Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral, triple yellow striped or solid yellow. Black neutrals may be specified if desired.
Standards
  • UL Standard 854 for Type USE-2
  • ASTM B-230, B-231 and ICEA S-105-692
  • Federal Specification JC-30B NEC
600V Secondary UD - Quadruplex
600 Volt Quadruplex
Code WordPhase ConductorsNeutral ConductorSingle Phase Conductor (in)Outside Diameter (in)Weight per 1000 ft. (lbs)Ampacity
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandInsulation Thickness (MLS)Direct BurialIn Duct
Tulsa47/w6047/w60.345.83325811985
Dyke27/w6047/w60.403.938346153115
Wittenberg27/w6027/w60.403.973375153115
Notre Dame1/019/w8027/w60.5221.188541198150
Purdue1/019/w801/019/w80.5221.260596198150
Syracuse2/019/w80119/w80.5661.316664225170
Wake Forest4/019/w802/019/w80.6721.560979290225
Rust25037/w953/019/w80.7481.7251,176319240
Slippery Rock35037/w954/019/w80.8511.9451,544385305
Wofford50037/w9535037/w95.8512.3482,174467420
Westminster75061/w11035037/w95.9792.7222,816615492

Ampacity: 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor for three conductor triplex with neutral carrying only unbalanced load.

All Yellow Extruded Stripe, cable is XLP insulation.

* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.

The above data are approximate and subject to normal manufacturing tolerances.