All Spec Sheets
Electro Cable
Service Drop Triplex
Aluminum URD & Overhead|Aluminum
(847) 376-9187 · (954) 526-8042·sales@electrocable.us
Application

To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75°C maximum for polyethylene insulation or 90°C maximum for crosslinked polyethylene (XLP) insulated conductors.

Product Features
  • Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR.
Standards

Service drop cable meets or exceeds the following ASTM specifications:

  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
  • B-231 Aluminum Conductors, Concentric-Lay-Stranded
  • B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
  • B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors
  • B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
  • ANSI/ICEA S-76-474
AAAC-Alloy Neutral Messenger
Service Drop Triplex
Code WordPhase ConductorsBare NeutralWeight per 1000 ft. (lbs)Rating (AMPS)
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandBreaking Strength (lbs)XLPPolyXLPPoly
Minex6Solid45671,110106.6102.98570
Hippa67/w45671,110107.0105.78570
Prawn4Solid45471,760158.4154.111090
Barnacles47/w45471,760160.0157.011090
Shrimp27/w45272,800243.0238.0150115
Gammarus1/07/w601/074,460390.0384.0200155
Leda1/019/w601/074,460384.0378.0200155
Dungenese2/07/w602/075,390481.0474.0230180
Cyclops2/019/w602/075,390473.0467.0230180
Flustra3/019/w603/076,790596.0589.1260205
Lepas4/019/w604/078,560725.0716.0300235
AAAC Alloy Reduced Neutral Messenger
Service Drop Triplex
Code WordPhase ConductorsBare NeutralWeight per 1000 ft. (lbs)Rating (AMPS)
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandBreaking Strength (lbs)XLPPolyXLPPoly
Artemia4Solid45671,110134.0132.011090
Crab47/w45671,110144.0141.211090
Solaster27/w45471,760216.0212.6150115
Sandcrab1/07/w60272,800348.0341.0200155
Echinus1/019/w60272,800342.0336.0200155
Crayfish2/07/w60173,530452.6422.5230180
Sipho2/019/w60173,530441.0422.5230180
Fulgar3/019/w601/074,460525.0518.0260205
Arca4/019/w602/075,360640.0632.0300235
AAC Neutral Messenger
Service Drop Triplex
Code WordPhase ConductorsBare NeutralWeight per 1000 ft. (lbs)Rating (AMPS)
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandBreaking Strength (lbs)XLPPolyXLPPoly
Haiotis6Solid4567563102.598.88570
Patella67/w4567563104.0101.68570
Fusus4Solid4547881151.9147.611090
Oyster47/w4547881154.0151.711090
Clam27/w45271,350232.0228.0150115
Murex1/07/w601/071,990374.0367.0200155
Purpura1/019/w601/071,990368.0362.0200155
Nassa2/07/w602/072,510461.0453.0230180
Melita3/019/w603/0193,310585.2562.9260205
Portunus4/019/w604/0194,020693.0684.0300235
Nannynose336.419/w80336.4196,1461,111.01,096.0380290
Full Size ACSR Messenger
Service Drop Triplex
Code WordPhase ConductorsBare NeutralWeight per 1000 ft. (lbs)Rating (AMPS)
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandBreaking Strength (lbs)XLPPolyXLPPoly
Paludina6Solid4566/11,1901141138570
Voluta67/w4566/11,1901151128570
Whelk4Solid4546/11,86016316111090
Periwinkle47/w4546/11,86017216911090
Conch27/w4526/12,850262257150115
Neritina1/07/w601/06/14,380420414200115
Cenia1/019/w601/06/14,380414408200115
Runcina2/07/w602/06/15,310519512230180
Triton2/019/w602/06/15,310511505230180
Cherrystone3/07/w603/06/16,620656643260205
Mursia3/019/w603/06/16,620633626260205
Razor4/07/w604/06/18,350814799300235
Zuzara4/019/w604/06/18,350785777300235
Limpet336.419/w80336.418/18,6801,1601,147300290
ACSR Reduced Size Messenger
Service Drop Triplex
Code WordPhase ConductorsBare NeutralWeight per 1000 ft. (lbs)Rating (AMPS)
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandBreaking Strength (lbs)XLPPolyXLPPoly
Scallop4Solid4566/11,19014213911090
Strombus47/w4566/11,19015114811090
Cockle27/w4546/11,860228224150115
Janthina1/07/w6026/12,850367360200155
Ranella1/019/w6026/12,850361356200155
Cavolinia2/07/w6016/13,550452444230180
Clio2/019/w6016/13,550444437230180
Sanddollar3/07/w601/06/14,380570557260205
Aega3/019/w601/06/14,380565552260205
Cutlefish4/07/w602/06/15,310706691300235
Cerapus4/019/w602/06/15,310678670300235
Cowry336.419/w804/06/18,3501,1351,093380290

* Note: Designated sizes are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201. Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft/sec. wind in sun.

** To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.

The data is approximate and subject to normal manufacturing tolerances.