All Spec Sheets
Electro Cable
Service Drop Duplex
Aluminum URD & Overhead|Aluminum
(847) 376-9187 · (954) 526-8042·sales@electrocable.us
Application

To supply 120 volts aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.

Product Features
  • Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR.
Standards

Service drop cable meets or exceeds the following ASTM specifications:

  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
  • B-231 Aluminum Conductors, Concentric-Lay-Stranded
  • B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)
  • B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors
  • B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire
  • ANSI/ICEA S-76-474
AAC Neutral Messenger
Service Drop Duplex
Code WordPhase ConductorsBare NeutralWeight per 1000 ft. (lbs)Rating (AMPS)
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandBreaking Strength (lbs)XLPPolyXLPPoly
Peakingese6Solid4567/w56363.561.78570
Collie67/w4567/w56366.863.18570
Dachshund4Solid4547/w88195.593.411090
Spaniel47/w4547/w881100.595.411090
Doberman27/w4527/w1,350152.7145.7150120
Malamute1/019/w601/07/w1,990242.6234.2205160
ACSR Neutral Messenger
Service Drop Duplex
Code WordPhase ConductorsBare NeutralWeight per 1000 ft. (lbs)Rating (AMPS)
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandBreaking Strength (lbs)XLPPolyXLPPoly
Setter6Solid4566/11,19075.073.28570
Shepherd67/w4566/11,19078.374.68570
Eskimo4Solid4546/11,860113.7111.611090
Terrier47/w4546/11,860118.7113.611090
Chow27/w4526/12,850181.7174.7150120
Bull1/019/w601/06/14,380288.7280.3200160
AAAC Alloy Neutral Messenger
Service Drop Duplex
Code WordPhase ConductorsBare NeutralWeight per 1000 ft. (lbs)Rating (AMPS)
Size AWGStrandInsulation Thickness (MLS)Size AWGStrandBreaking Strength (lbs)XLPPolyXLPPoly
Chihuahua6Solid4567/w1,11067.665.88570
Vizsla67/w4567/w1,11070.967.28570
Harrier4Solid4547/w1,760102.099.911090
Whippet47/w4547/w1,760107.0101.911090
Schnauzer27/w4527/w2,800163.3156.2150120
Heeler1/019/w601/07/w4,460259.2250.8200160

* Note: Designated sizes are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201. Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft/sec. wind in sun.

** To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.

The data is approximate and subject to normal manufacturing tolerances.