All Spec Sheets
Electro Cable
USE-RHH-RHW-2 Aluminum
Aluminum Building Wire|Aluminum
(847) 376-9187 · (954) 526-8042·sales@electrocable.us
Application

Type USE-RHH-RHW-2 building wire and service cable is recognized for use as general purpose wiring at a maximum conductor temperature of 90°C in wet or dry locations for installation in air, conduit or other recognized raceways and for direct burial in circuits not exceeding 600 volts.

Product Features
  • Compact stranded 8000 Series aluminum alloy conductor.
  • Insulation is an abrasion, moisture, heat and sunlight resistant black cross-linked polyethylene (XLPE).
Standards
  • UL Standard 44 (RHW or RHH), UL Standard 854 (USE) and Federal Specification JC-30B NEC.
USE-RHH-RHW-2
USE-RHH-RHW-2 Aluminum
Cond. Size AWG or MCMStrandingInsulation Thickness (mils)Outside Diameter (in)Weight per 1000 ft. (lbs)Ampacity (amps) 90° C
67/w60.2904960
47/w60.3346575
27/w60.39094100
119/w80.460125115
1/019/w80.500150135
2/019/w80.540181150
3/019/w80.590220175
4/019/w80.635268205
25037/w95.710320230
35037/w95.810428280
50037/w95.930591350
60061/w1101.035715385
75061/w1101.130873435
100061/w1101.2801132500

1. Data are approximate and subject to normal manufacturing tolerances.

2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%

3. Two, Three or four conductors can be paralleled on a reel.

4. 90°C-RHH dry locations, RHW-2 wet or dry locations.